HSLCH – JZ

Catégorie :

Request a quote

7 + 11 =

APPLICATIONS

LSOH cable For the electrical interconnection of components of production facilities and machine tools if a certain level of screening is required. This cable is intended for indoor use.

CONDUCTOR CONSTRUCTION

Copper fine stranded class 5

TECHNICAL DATA

Nominal voltage Uo : 300 V
Nominal voltage U : 500 V
Test voltage : 2KV , 5 min
Insulation resistance : Min 20 Mohm x km

OTHER CHARACTERISTICS

Max permissible temperature at conductor :

  • In operation : +70° C
  • In short circuit : +150° C

Max operating temperature, fixed : -40 - +70° C
Temperature, moved, during installation: -5 - +70° C
Bending radius, fixed installation : 6Xd
Bending radius, moved application : 20Xd

CORE IDENTIFICATION

For HSLCH-JZ: Numbers and green yellow for the protective conductor

FIRE PROPERTIES

Flame retardant : IEC 60332-3-24 CAT C
Combustion gases: EN 50267
Acidity of gases : IEC 60754

Download (50.7k)

Informations complémentaires

Core

Insulation

BANDING

Polyester tape

SCREENING

Braiding of tinned copper wires
Coverage: 70%.

Outer Sheath